업무관련자료/전기관련자료

[스크랩] 전선 규격별 허용전류표 (개정)

한뫼 박종근 2007. 12. 26. 09:56

C절연(IV)전선 허용전류(도체온도는 70℃, 주위온도 30℃ 기준)

mm2

단상

삼상

1회로

2회로

3회로

4회로

5회로

1회로

2회로

3회로

4회로

5회로

1.5

2.5

4

6

10

16

25

14.5

19.5

26

34

46

61

80

11.6

15.6

20.8

27.2

36.8

48.8

64

8.1

13.7

18.2

23.8

32.2

42.7

56

9.4

12.7

16.9

22.1

29.9

39.7

52

7.0

11.7

15.6

20.4

27.6

36.6

48

13.5

18

24

31

42

56

73

10.8

14.4

19.2

24.8

33.6

44.8

58.4

9.5

12.6

16.8

21.7

29.4

39.2

51.1

8.8

11.7

15.6

20.2

27.3

36.4

47.5

8.1

10.8

14.4

18.6

25.2

33.6

43.8

35

50

70

95

120

150

185

240

300

99

119

151

182

210

240

273

321

367

79.2

95.2

120.8

145.6

168

192

218.4

256.8

293.6

69.3

83.3

105.7

127.4

147

168

191.1

224.7

256.9

64.4

77.4

98.15

118.3

136.5

156

177.5

208.7

238.6

59.4

71.4

90.6

109.2

126

144

163.8

192.6

220.2

89

108

136

164

188

216

245

286

328

71.2

86.4

108.8

131.2

150.4

172.8

196

228.8

262.4

62.3

75.6

95.2

114.8

131.6

151.2

171.5

200.2

229.6

57.9

70.2

88.4

106.6

122.2

140.4

159.3

185.9

213.2

53.4

64.8

81.6

98.4

112.8

129.6

147

171.6

196.8

 

내열PVC절연(HIV)전선 허용전류

1.5

2.5

4

6

10

16

25

19

26

35

45

61

81

106

15.2

20.8

28

36

48.8

64.8

84.8

13.3

18.2

24.5

31.5

42.7

56.7

74.2

12.4

16.9

22.8

29.3

39.7

52.7

68.9

11.4

15.6

21

27

36.6

48.6

63.6

17

23

31

40

54

73

95

13.6

18.4

24.8

32

43.2

58.4

76

11.9

16.1

21.7

28

30.2

51.1

66.5

11.1

15

20.2

26

35.1

47.5

61.8

10.2

13.8

18.6

24

32.4

43.8

57

35

50

70

95

120

150

185

240

300

131

158

200

241

278

318

362

424

486

104.8

126.4

160

192.8

222.4

254.4

289.6

339.2

388.8

91.7

110.6

140

168.7

194.6

222.6

253.4

296.8

340.2

85.2

102.7

130

156.7

180.7

206.7

235.3

275.6

315.9

78.6

94.8

120

144.6

166.8

190.8

217.2

254.4

291.6

117

141

179

216

249

285

324

380

435

93.6

112.8

143.2

172.8

199.2

228

259.2

304

348

81.9

98.7

125.3

151.2

174.3

199.5

226.8

266

304.5

76.1

91.7

116.4

140.4

161.9

185.3

210.6

247

282.75

70.2

84.6

107.4

129.6

149.4

171

194.4

228

261

 

첨부파일 :

첨부파일 배선설비의_허용전류와_공사방법.hwp


 

 

출처 : 보일러,냉동,가스,건축설비
글쓴이 : 다움이[전석진] 원글보기
메모 :