◈ 케이블 연장시 전선규격 적용표
가동 방식 |
케이블길이 출력(Kw)전류(A) |
케이블사이즈(㎟)상단220V,하단380V or 440V | ||||||||||
50m |
60m |
70m |
80m |
90m |
100m |
120m |
140m |
160m |
180m | |||
직 입 기 동 |
0.75 |
3.5 2.0 |
0.75 0.75 |
0.75 0.75 |
1.25 0.75 |
1.25 0.75 |
2.0 1.25 |
2.0 1.25 |
2.0 1.25 |
2.0 2.0 |
3.5 2.0 |
1.5 2.0 |
1.5 |
7 4.0 |
1.25 0.75 |
1.25 0.75 |
2.0 1.25 |
2.0 1.25 |
3.5 2.0 |
3.5 2.0 |
3.5 2.0 |
3.5 2.0 |
5.5 3.5 |
5.5 3.5 | |
2.2 |
11 6.5 |
2 1.25 |
2.0 1.25 |
3.5 2.0 |
3.5 2.0 |
3.5 2.0 |
3.5 2.0 |
5.5 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 | |
3.7 |
10 10.5 |
3.5 2.0 |
3.5 2.0 |
3.5 3.5 |
5.5 3.5 |
5.5 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
14.0 8.0 |
14.0 8.0 | |
5.5 |
26 15 |
5.5 3.5 |
5.5 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
8.0 5.5 |
14.0 8.0 |
14.0 8.0 |
14.0 8.0 |
14.0 8.0 | |
7.5 |
34 21 |
5.0 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
140 8.0 |
14.0 8.0 |
14.0 8.0 |
22.0 14.0 |
22.0 14.0 |
22.0 14.0 | |
11 |
48 28 |
8.0 5.5 |
14.0 8.0 |
14.0 8.0 |
14.0 8.0 |
22.0 8.0 |
22.0 8.0 |
22.0 8.0 |
22.0 8.0 |
30.0 22.0 |
30.0 22.0 | |
15.75 |
65 37 |
14 8 |
14 8 |
14 8 |
22 14 |
22 14 |
22 14 |
22 14 |
30 22 |
38 22 |
38 22 | |
19 |
75 38 |
14 8 |
22 14 |
22 14 |
22 14 |
22 14 |
30 14 |
30 22 |
38 22 |
50 22 |
50 30 | |
22 |
85 49 |
22 14 |
22 14 |
22 14 |
30 14 |
30 14 |
30 22 |
30 22 |
38 30 |
50 30 |
50 30 | |
스 타 엘 타 기 동 |
11 |
48 28 |
5.5 3.5 |
5.5 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
14 8 |
14 8 |
24 8 |
22 8 |
22 14 |
15 |
65 37 |
8.0 5.5 |
8.0 5.5 |
8.0 5.5 |
14 8 |
14 8 |
24 8 |
22 8 |
22 14 |
22 14 |
22 14 | |
19 |
75 38 |
8.0 5.5 |
8.0 5.5 |
14 8 |
14 8 |
14 8 |
14 8 |
14 14 |
22 14 |
30 14 |
30 14 | |
22 |
85 89 |
14 5.5 |
14 5.5 |
14 8 |
14 8 |
22 8 |
22 14 |
22 14 |
30 14 |
30 22 |
30 22 | |
26 |
100 58 |
14 8 |
14 8 |
14 8 |
22 8 |
22 14 |
22 14 |
30 14 |
30 22 |
38 22 |
38 22 | |
30 |
115 66 |
14 8 |
14 8 |
22 8 |
22 14 |
22 14 |
30 14 |
30 22 |
38 22 |
38 22 |
50 22 | |
37 |
140 81 |
22 14 |
22 14 |
22 14 |
22 14 |
30 14 |
30 14 |
38 22 |
50 22 |
50 22 |
50 22 | |
45 |
185 107 |
22 14 |
22 14 |
30 14 |
30 14 |
38 14 |
38 14 |
50 22 |
60 30 |
60 30 |
- - | |
55 |
220 127 |
30 14 |
30 14 |
30 14 |
38 22 |
38 22 |
50 22 |
60 30 |
- - |
- - |
- - | |
75 |
300 173 |
38 22 |
38 22 |
50 22 |
50 30 |
60 30 |
60 30 |
- - |
- - |
- - |
- - |